AHU Airflow Sizing Calculator
Supply airflow, coil face area and equivalent duct diameter from a cooling load and supply-return ΔT. First-pass sizing to challenge over-specified plant.
Inputs
Result
Supply mass flow11.94 kg/s
Supply airflow9917 L/s
Supply airflow35702 m³/h
Coil face area3.97 m²
Main duct area1.65 m²
Equivalent round duct1451 mm Ø
How this works
Q = ṁ · cp · ΔT with cp,air = 1.005 kJ/kg·K and ρ = 1.204 kg/m³. Coil face velocity above ~2.8 m/s risks moisture carry-over on wet coils.
Main duct velocities of 5-7 m/s balance acoustics against space. Above 8 m/s consider acoustic attenuators and larger risers.